First Power-On
Power-on sequence and initial system verification.
Before Powering On
⚠️ Both Lids Must Be Removed:
- Rear lid: Required for power cable access to PDU
- Front lid: Required for airflow inlet to internal components (prevents overheating)
- Never operate with lids closed - critical for cooling and access
Optional - Network Uplink:
- Uplink cable NOT connected for initial power-on (prevents DHCP conflicts)
- Will connect uplink after initial verification
Note: We'll connect the power cable as part of the power-on sequence below.
Power-On Sequence
Step 1: Connect Power Cable
EDC will boot automatically and begin powering the system components once power cable is inserted.
-
Locate the PDU on the Rear Panel
- PDU is mounted on the bottom of the rear panel
- Power inlet is on the left side of the PDU
-
Plug the Power Cable into the PDU
- Take the included power cable
- Insert the IEC C13 connector into the PDU power inlet
- Push firmly until fully seated
-
Plug the Other End into the Wall Outlet
- Use a grounded 3-prong outlet
- North America: 110-120V outlet
- International: 220-240V outlet
-
Verify PDU Powers On
- PDU LCD display should light up within 2-3 seconds
- Display shows voltage and power consumption after it is fully booted (30-60s)
- Initial reading will be low (only PDU and switch powered initially)
Step 2: Verify Switch Power-On
The EnGenius switch should power on automatically when main power is enabled and PDU is booted.
Verification:
- Look for LED indicators on the switch
- Power LED should be solid green
- Port LEDs will illuminate as devices connect
- May take 30-60 seconds for full boot
Normal Behavior:
- Switch boots and runs self-test
- Some LEDs may flash during startup
- Port LEDs light as internal devices connect
Step 3: Power On Compute Nodes
Compute nodes may require manual power-on depending on the UEFI configuration.
Press the button on the front face of each compute node.
The light on the button will illuminate to signify the node working.
Initial Power-On Verification
PDU Display Check
Look at the PDU LCD Display:
- Voltage: Should show 100-120V (NA) or 200-240V (International)
- Current: Will increase as nodes boot
- Power: Total system power consumption
Typical Readings After Full Power-On:
- NUC Edition: 200-400W
- HR-01-2 Edition: 300-600W
- HR-01-4 Edition: 500-900W (estimated)
Do note that these are estimated and will vary based on the actual load of your nodes.
If Voltage Reading is Incorrect:
- Verify correct input voltage at outlet
- Check power cable connections
- See troubleshooting section below
Switch Status Check
Check the Switch LED Indicators:
- Power LED: Solid green
- Port LEDs: Blinking
Cooling System Check
Listen For Fan Operation:
- Cooling fans should be audible from rear of EDC
- Initial fan speed may be higher during boot
- Fan speed should stabilize after 2-3 minutes
- Airflow should be felt at rear exhaust vents
Note: EDC active cooling fans are temperature controlled, and depending on the ambient temperature may not turn on.
Feel Rear Exhaust:
- Place hand near rear panel vents
- Should feel slight airflow
- Air will warm up as system runs
Compute Node Verification
For Each Compute Node:
- Power LED lit (indicates node is running)
- Network activity LEDs blinking on node network ports
- Fan noise from each node
- No error beeps or alarm sounds
HCI Software Startup:
- May take additional 2-5 minutes after OS boots
- Nodes will join cluster automatically (if pre-configured by your reseller)
- Access via HCI management interface (see next steps)
Normal First Boot Behavior
What You Should Observe:
- PDU powers on immediately (~30 seconds)
- Switch boots (30-60 seconds)
- Compute nodes boot when powered on (30-120 seconds per node)
- System becomes stable within 5 minutes total
Normal Sounds:
- Fan noise (varies by cooling profile)
- No beeping, clicking, or alarm sounds
Normal Temperature Progression:
- System starts cool
- Temperature rises during first 10-15 minutes
- Fans may increase speed temporarily
- System stabilizes at normal operating temperature
Troubleshooting
Nothing Powers On - No PDU Display
Problem: No power to any component
Check:
- Power cable fully inserted at both ends (PDU inlet and wall outlet)
- Wall outlet has power (test with another device)
- Circuit breaker not tripped
- Extension cord or power strip functioning (if used)
- PDU inlet connection is secure
If Still No Power:
- Contact your reseller immediately
- Do not attempt internal inspection
- May be PDU or wiring issue
PDU Powers On But Switch Does Not
Problem: PDU LCD lit but switch has no LEDs
Check:
- Wait 60 seconds - switch may still be booting
- Look carefully at switch - some LEDs are small
- Check internal power connection from PDU to switch (if qualified)
If Switch Does Not Power On After 2 Minutes:
- Contact your reseller
- Switch may require service
- Possible internal cable issue
Compute Nodes Won't Power On
Problem: Pressing power button has no effect
Check:
- Verify PDU is powered on (LCD lit)
- Check power cable connection to each node
- Try holding power button for 2-3 seconds
If Nodes Still Won't Power On:
- Verify outlet power cycling hasn't disabled PDU outlets
- Check PDU display for outlet status (make sure it is enabled)
Fans Running Very Loud / Not Running
Problem: Fan noise excessive or absent
Fans Very Loud:
- May be normal during initial boot (high speed startup)
- Should stabilize within 3-5 minutes
- If remains loud, may be set to Turbo profile
- If your ambient temperature is high, it is expected to run louder
- See Cooling Management
Safety - When to Power Off Immediately
Power Off the System Immediately if You Observe:
- ⚠️ Smoke or burning smell
- ⚠️ Sparks or electrical arcing
- ⚠️ Continuous loud beeping/alarms
- ⚠️ Extremely hot surfaces (too hot to touch)
- ⚠️ Liquid leakage
- ⚠️ Unusual loud mechanical noise (grinding, clicking)
Emergency Shutdown Procedure:
- Unplug the power cable from the PDU immediately (if safe to do so)
- If unsafe to approach the rear panel, unplug from the wall outlet instead
- Contact reseller immediately
- Do not attempt to restart
- Document what you observed
What's Next?
After successful first power-on and verification:
👉 Initial Access - Access switch, PDU, and compute nodes
Or if you need to connect network first:
👉 Network Configuration - Configure network connectivity